A shared neutral is a connection in which a plurality of circuits use the same neutral connection. This is also known as a common neutral, and the circuits and neutral together are sometimes referred to as an Edison circuit. 

Is it OK to share a neutral?

Only if the breakers are tied together. The NEC requires that if two or 3 circuits have one neutral, thatall 2/3 breakers will shut down if one is turned off. The reason being that there will still be a load on the neutral making it a hazard.

How many hits can share a neutral?

If you use one neutral with two circuits you can exceed the capacity of the conductor and damage the conductor. In a 3 phase system you can have 3 hots on a single neutral because the current is 120º out of phase from each other and won’t add up like they do in a single phase system.

Why can’t you share neutrals?





When a current builds up on the neutral, the neutral can overheat. The additional current will cause the problem to be compounded when multiple circuits are connected to the shared neutral and buildup will occur.

How do you find shared neutral?


Quote from video: Simply hold the back of the receiver. Against the wall plate. Until you identify the highest numerical reading on drew Seaver at that location. Then continue scanning all the locations in the circuit.

Can a neutral trip a breaker?

Your Electrical System Has a Short Circuit



The simplest definition of a short circuit is contact between the neutral and the live wires. When the wires touch, it can cause your circuit breaker to trip immediately after turning it on. Contact between the live and neutral wires will cause a sudden flow in current.

Can a neutral wire trip a breaker?



A short circuit occurs when a hot or active electrical wire and a neutral wire touch. This meeting of the wires causes a large amount of current to flow and overload the circuit. A short circuit should always cause a breaker to trip or a fuse to blow. It might also cause sparks, popping sounds, and possibly some smoke.

Can you share neutral and ground?

The answer is never. Grounds and neutrals should only be connected at the last point of disconnect. This would be at main panels only.



Can three circuits share neutrals?

It is perfectly fine and within code.



The only stipulations are that you must splice the neutral, you cannot use the screws on one device to carry the neutral to the other, and that you must use a two-pole or handle-tied breaker. For reference, this is known as a multi-wire branch circuit.

What happens if the neutral is not bonded?

The dangers of a share neutral

What is the rule for a neutral wire?

The Code considers the neutral conductor a current-carrying conductor only when it carries the unbalanced current from other ungrounded phase conductors. When circuits are properly balanced, the neutral carries very little current.

How many wires can be under a neutral terminal?



Note: NEC allows only one current-carrying conductor per hole on the neutrals unless otherwise noted.

Can 2 20 amp circuits share a neutral?

Yes, you can share the same white for neutral on both circuits, you must use a double pole breaker or two adjacent single pole breakers with a handle tie, and your wiring must be done such that removing a device doesn’t interrupt the neutral – in other words, pigtail the neutrals.

Can 2 30 amp circuits share a neutral?

It is perfectly fine and within code. The only stipulations are that you must splice the neutral, you cannot use the screws on one device to carry the neutral to the other, and that you must use a two-pole or handle-tied breaker. For reference, this is known as a multi-wire branch circuit.

Can neutral and ground share the same bus?

The answer is never. Grounds and neutrals should only be connected at the last point of disconnect.

How many neutrals can be tied together?



300.3 references 310.4, tho 300.3 says all conductors of a circuit must be in the same cable, raceway, etc unless allowed elsewhere. Even if you meet that condition, you still cannot tie 2 or more #12 neutrals together.